Applications : | These cables are flame retardant, low smoke and halogen free, used for earthing and bonding services. |
Standards : | IEC 60092-353; IEC 60092-359; IEC 60332-1; IEC 60332-3-22; IEC 60754-1,2; IEC 61034-1,2; NEK 606:2004 |
Conductors : | Tinned annealed stranded copper to IEC 60228 class 2 or class 5. |
Insulation : | Halogen free thermosetting compound, SHF2. When used as protective earth (PE) wire, the cables coloured yellow/green. When used as single wire, the cables coloured off-white, black, red or blue. |
Electrical Characteristics :
Nominal Cross Section Area | mm² | 10 | 16 | 25 | 35 | 50 | 70 |
Nominal Conductor Diameter | mm | 4 | 5.1 | 6.5 | 7.4 | 8.7 | 10.3 |
Maximum DC Resistant@20℃ | Ω/km | 1.84 | 1.16 | 0.734 | 0.529 | 0.391 | 0.27 |
Continuous Current Rating@45℃1 Core | A | 72 | 96 | 127 | 157 | 196 | 242 |
Short Circuit Current 1s | A | 1430 | 2290 | 3580 | 5010 | 7150 | 10020 |
Operating Voltage | KV | 0.6/1 | 0.6/1 | 0.6/1 | 0.6/1 | 0.6/1 | 0.6/1 |
Mechanical and Thermal Properties :
Bending Radius : 8×OD (during installation); 6×OD (fixed installed).
Temperature Range : -20℃ ~ +90℃.
Dimensions and Weight :
Construction No. of cores×Cross section (mm²) | Nominal Insulation Thickness mm | Nominal Overall Diameter mm | Nominal Weight kg/km |
1×10 | 2.0 | 8.2 | 160 |
1×16 | 2.1 | 9.4 | 230 |
1×25 | 2.4 | 11.3 | 350 |
1×35 | 2.4 | 12.4 | 450 |
1×50 | 2.7 | 14.4 | 600 |
1×70 | 3.0 | 16.7 | 840 |
1×95 | 3.0 | 18.6 | 1110 |
1×120 | 3.1 | 20.3 | 1360 |
1×150 | 3.4 | 22.4 | 1660 |
1×185 | 3.7 | 24.9 | 2080 |
1×240 | 4.0 | 28.1 | 2690 |
1×300 | 4.3 | 31.0 | 3330 |
Applications : | These cables are flame retardant, low smoke and halogen free, used for earthing and bonding services. |
Standards : | IEC 60092-353; IEC 60092-359; IEC 60332-1; IEC 60332-3-22; IEC 60754-1,2; IEC 61034-1,2; NEK 606:2004 |
Conductors : | Tinned annealed stranded copper to IEC 60228 class 2 or class 5. |
Insulation : | Halogen free thermosetting compound, SHF2. When used as protective earth (PE) wire, the cables coloured yellow/green. When used as single wire, the cables coloured off-white, black, red or blue. |
Electrical Characteristics :
Nominal Cross Section Area | mm² | 10 | 16 | 25 | 35 | 50 | 70 |
Nominal Conductor Diameter | mm | 4 | 5.1 | 6.5 | 7.4 | 8.7 | 10.3 |
Maximum DC Resistant@20℃ | Ω/km | 1.84 | 1.16 | 0.734 | 0.529 | 0.391 | 0.27 |
Continuous Current Rating@45℃1 Core | A | 72 | 96 | 127 | 157 | 196 | 242 |
Short Circuit Current 1s | A | 1430 | 2290 | 3580 | 5010 | 7150 | 10020 |
Operating Voltage | KV | 0.6/1 | 0.6/1 | 0.6/1 | 0.6/1 | 0.6/1 | 0.6/1 |
Mechanical and Thermal Properties :
Bending Radius : 8×OD (during installation); 6×OD (fixed installed).
Temperature Range : -20℃ ~ +90℃.
Dimensions and Weight :
Construction No. of cores×Cross section (mm²) | Nominal Insulation Thickness mm | Nominal Overall Diameter mm | Nominal Weight kg/km |
1×10 | 2.0 | 8.2 | 160 |
1×16 | 2.1 | 9.4 | 230 |
1×25 | 2.4 | 11.3 | 350 |
1×35 | 2.4 | 12.4 | 450 |
1×50 | 2.7 | 14.4 | 600 |
1×70 | 3.0 | 16.7 | 840 |
1×95 | 3.0 | 18.6 | 1110 |
1×120 | 3.1 | 20.3 | 1360 |
1×150 | 3.4 | 22.4 | 1660 |
1×185 | 3.7 | 24.9 | 2080 |
1×240 | 4.0 | 28.1 | 2690 |
1×300 | 4.3 | 31.0 | 3330 |