Availability: | |
---|---|
Quantity: | |
Application
Suitable for connecting instruments and control systems for analogue or digital signal transmission. Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations
Construction
Conductor: | Solid, stranded or flexible plain or metal coated copper in accordance with class1, 2 or 5 of | |
HD383 in the range of 0.5mm2 to 2.5mm2. | ||
Fire Barrier: | Mica tape. | |
Insulation: | XLPE to EN 50290. Suitable alternative materials are under consideration. |
Triples Identification: Black&White&Red color with number on the cores for multi pairs, start with 1 in the centre.
Individual Screen: Aluminimum foil tape over a tinned copper drain wire.
Wrapping: At least 1 layer of plastic tape.
Collective Screen: Aluminimum foil tape over a tinned copper drain wire.
Outer Sheath: Halogen free flame retardant compound LSZH, to EN 50290-2-27.
Electrical data at 20°C
Character | Unit | Values | |||||
Conductor size | nom. | mm² | 0.5 | 0.75 | 1.0 | 1.5 | |
Conductor resistance | max. | Ω/km | 36.7 | 25.0 | 18.5 | 12.3 | |
Insulation resistance | min. | MΩ x km | 5000 | ||||
L/R (ratio) | max. | µH/Ω | 25 | 40 | |||
Inductance | max. | mH/km | 1 | ||||
Mutual capacitance | max. | nF/m | 100 | 100 | |||
Test voltage | V | 2000 | |||||
Operating voltage U0 / U | max. | V | 500 |
Application
Suitable for connecting instruments and control systems for analogue or digital signal transmission. Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations
Construction
Conductor: | Solid, stranded or flexible plain or metal coated copper in accordance with class1, 2 or 5 of | |
HD383 in the range of 0.5mm2 to 2.5mm2. | ||
Fire Barrier: | Mica tape. | |
Insulation: | XLPE to EN 50290. Suitable alternative materials are under consideration. |
Triples Identification: Black&White&Red color with number on the cores for multi pairs, start with 1 in the centre.
Individual Screen: Aluminimum foil tape over a tinned copper drain wire.
Wrapping: At least 1 layer of plastic tape.
Collective Screen: Aluminimum foil tape over a tinned copper drain wire.
Outer Sheath: Halogen free flame retardant compound LSZH, to EN 50290-2-27.
Electrical data at 20°C
Character | Unit | Values | |||||
Conductor size | nom. | mm² | 0.5 | 0.75 | 1.0 | 1.5 | |
Conductor resistance | max. | Ω/km | 36.7 | 25.0 | 18.5 | 12.3 | |
Insulation resistance | min. | MΩ x km | 5000 | ||||
L/R (ratio) | max. | µH/Ω | 25 | 40 | |||
Inductance | max. | mH/km | 1 | ||||
Mutual capacitance | max. | nF/m | 100 | 100 | |||
Test voltage | V | 2000 | |||||
Operating voltage U0 / U | max. | V | 500 |