RE-2X(St)H 90°C / 300 V
STANDARDS | Basic design to EN 50288-7 |
APPLICATION | Instrument cable minimizes noise and signal interference, delivering clean signals in harsh environments and general manufacturing operations. |
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)*** | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Sunlight Resistance | UL 1581 section 1200 |
Oil Resistance** | ICEA S-73-532 |
Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation, *** denotes optional.
VOLTAGE RATING | 300V |
CABLE CONSTRUCTION | |
Conductor: | Annealed copper solid or plain copper stranded to IEC 60228 Class 2. |
Insulation: | Extruded cross-linked XLPE compound, EN 50290. 2-29. |
Triple: | Three conductors twisted to form a triple |
Lay-up: | Triples laid up in layers of optimum pitch |
Separator: | Polyester tape |
Overall Screen: | Aluminium/polyester tape with tinned copper drain wire, 0.5mm2 |
Outer Sheath: | Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. |
COLOUR CODE | |
Insulation: | Black / White / Red, continuously numbered on white core(1, 2..)for multitriples. |
Outer Sheath: | Black or blue for intrinsically safe systems |
Physical AND THERMAL PROPERTIES | |
Temperature Range During Operation (Fixed State): | -30°C – +90°C |
Temperature Range During Installation (Mobile State): | -5°C – +50°C |
Minimum Bending Radius: | 7.5 X Overall Diameter |
CONSTRUCTION PARAMETERS
Cable Code | RE-2X(St)YH | ||||
No. of Triples x3xCross Section | Nominal Insulation Thickness | Nominal Outer Sheath Thickness | Nominal Overall Diameter | Approx. Weight | |
No.x3xmm2 | mm | mm | mm | kg/km | |
RE-2X(St)H 1T0.5 | 1x3x0,50 | 0.35 | 0.8 | 5.4 | 45 |
RE-2X(St)H 1T0.75 | 1x3x0,75 | 0.38 | 0.9 | 6.1 | 59 |
RE-2X(St)H 1T1.0 | 1x3x1.0 | 0.4 | 0.9 | 6.6 | 66 |
RE-2X(St)H 1T1.3 | 1x3x1,3 | 0.45 | 0.9 | 7.2 | 86 |
RE-2X(St)H 1T1.5 | 1x3x1,5 | 0.45 | 0.9 | 7.5 | 95 |
Note : Other conductor sizes & core configurations are available upon request.
Electrical PROPERTIES
Conductor Area Size | mm 2 | 0.5 | 0.75 | 1.0 | 1.3 | 1.5 | |
Insulation thickness (nominal) | mm | 0.35 | 0.38 | 0.4 | 0.45 | 0.45 | |
Conductor resistance (20°C) | Ω/km | 36.7 | 25.0 | 18.5 | 14.2 | 12.3 | |
Insulation resistance (20°C) | MΩ.km(Min.) | 5000 | 5000 | 5000 | 5000 | 5000 | |
Mutual Capacitance (1 kHz) | pF/m(Max.) | 115 | |||||
Inductance | mH/km(Max.) | 1 | |||||
L / R (ratio) (max.) | μH/Ω | 25 | 25 | 25 | 40 | 40 | |
Operating voltage | V | 300 | |||||
Test Voltage Urms | Core to Core | V | 1500 | ||||
Core to Screen | V | 1500 |
RE-2X(St)H 90°C / 300 V
STANDARDS | Basic design to EN 50288-7 |
APPLICATION | Instrument cable minimizes noise and signal interference, delivering clean signals in harsh environments and general manufacturing operations. |
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)*** | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Sunlight Resistance | UL 1581 section 1200 |
Oil Resistance** | ICEA S-73-532 |
Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation, *** denotes optional.
VOLTAGE RATING | 300V |
CABLE CONSTRUCTION | |
Conductor: | Annealed copper solid or plain copper stranded to IEC 60228 Class 2. |
Insulation: | Extruded cross-linked XLPE compound, EN 50290. 2-29. |
Triple: | Three conductors twisted to form a triple |
Lay-up: | Triples laid up in layers of optimum pitch |
Separator: | Polyester tape |
Overall Screen: | Aluminium/polyester tape with tinned copper drain wire, 0.5mm2 |
Outer Sheath: | Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. |
COLOUR CODE | |
Insulation: | Black / White / Red, continuously numbered on white core(1, 2..)for multitriples. |
Outer Sheath: | Black or blue for intrinsically safe systems |
Physical AND THERMAL PROPERTIES | |
Temperature Range During Operation (Fixed State): | -30°C – +90°C |
Temperature Range During Installation (Mobile State): | -5°C – +50°C |
Minimum Bending Radius: | 7.5 X Overall Diameter |
CONSTRUCTION PARAMETERS
Cable Code | RE-2X(St)YH | ||||
No. of Triples x3xCross Section | Nominal Insulation Thickness | Nominal Outer Sheath Thickness | Nominal Overall Diameter | Approx. Weight | |
No.x3xmm2 | mm | mm | mm | kg/km | |
RE-2X(St)H 1T0.5 | 1x3x0,50 | 0.35 | 0.8 | 5.4 | 45 |
RE-2X(St)H 1T0.75 | 1x3x0,75 | 0.38 | 0.9 | 6.1 | 59 |
RE-2X(St)H 1T1.0 | 1x3x1.0 | 0.4 | 0.9 | 6.6 | 66 |
RE-2X(St)H 1T1.3 | 1x3x1,3 | 0.45 | 0.9 | 7.2 | 86 |
RE-2X(St)H 1T1.5 | 1x3x1,5 | 0.45 | 0.9 | 7.5 | 95 |
Note : Other conductor sizes & core configurations are available upon request.
Electrical PROPERTIES
Conductor Area Size | mm 2 | 0.5 | 0.75 | 1.0 | 1.3 | 1.5 | |
Insulation thickness (nominal) | mm | 0.35 | 0.38 | 0.4 | 0.45 | 0.45 | |
Conductor resistance (20°C) | Ω/km | 36.7 | 25.0 | 18.5 | 14.2 | 12.3 | |
Insulation resistance (20°C) | MΩ.km(Min.) | 5000 | 5000 | 5000 | 5000 | 5000 | |
Mutual Capacitance (1 kHz) | pF/m(Max.) | 115 | |||||
Inductance | mH/km(Max.) | 1 | |||||
L / R (ratio) (max.) | μH/Ω | 25 | 25 | 25 | 40 | 40 | |
Operating voltage | V | 300 | |||||
Test Voltage Urms | Core to Core | V | 1500 | ||||
Core to Screen | V | 1500 |