RE-2Y(C)H 90°C / 300V
STANDARDS | Basic design to EN 50288-7 |
APPLICATION | Instrument cable minimizes noise and signal interference, delivering clean signals in harsh environments and general manufacturing operations. |
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Sunlight Resistance | UL 1581 section 1200 |
Oil Resistance | ICEA S-73-532** |
Note: Asterisk * denotes superseded standard, **Test temperature +60°C, duration 4h. Retention: min 60% of tensite strength/min.60% of elongation.
VOLTAGE RATING | 300V |
CABLE CONSTRUCTION | |
Conductor: | Annealed copper solid or plain copper stranded to IEC 60228 Class 2. |
Insulation: | PE compound, EN 50290. 2-23. |
Pair: | Two conductors twisted to form a pair |
Lay-up: | Pairs laid up in layers of optimum pitch |
Separator: | Polyester tape |
Overall Screen: | Tinned copper wire braid |
Outer sheath: | Thermoplastic LSZH compound type to EN 50290-2-27. |
COLOUR CODE | |
Insulation: | Black / White, continuously numbered on white core(1, 2..)for multipair. |
Outer Sheath: | Black or blue for intrinsically safe systems |
Physical AND THERMAL PROPERTIES | |
Temperature Range During Operation (Fixed State): | -30°C – +70°C |
Temperature Range During Installation (Mobile State): | -5°C – +50°C |
Minimum Bending Radius: | 7.5 X Overall Diameter |
CONSTRUCTION PARAMETERS
Cable Code | RE-2Y(C)H | ||
No. of Pairsx2xCross Section | Copper Weight | Approx. Weight | |
No.x2xmm2 | Kg/km | Kg/km | |
0.5mm2, Multipair | |||
RE-2Y(C)H 1P0.5 | 1x2x0.50 | 8.3 | 110 |
RE-2Y(C)H 2P0.5 | 2x2x0.50 | 10.7 | 143 |
RE-2Y(C)H 3P0.5 | 3x2x0.50 | 11.1 | 158 |
RE-2Y(C)H 4P0.5 | 4x2x0.50 | 11.9 | 181 |
RE-2Y(C)H 6P0.5 | 6x2x0.50 | 13.6 | 230 |
RE-2Y(C)H 8P0.5 | 8x2x0.50 | 14.2 | 264 |
RE-2Y(C)H 12P0.5 | 12x2x0.50 | 16.4 | 343 |
RE-2Y(C)H 16P0.5 | 16x2x0.50 | 18.2 | 418 |
RE-2Y(C)H 20P0.5 | 20x2x0.50 | 19.7 | 487 |
RE-2Y(C)H 24P0.5 | 24x2x0.50 | 21.1 | 557 |
0.75mm2, Multipair | |||
RE-2Y(C)H 1P0.75 | 1x2x0.75 | 8.7 | 119 |
RE-2Y(C)H 2P0.75 | 2x2x0.75 | 11.4 | 161 |
RE-2Y(C)H 3P0.75 | 3x2x0.75 | 11.9 | 185 |
RE-2Y(C)H 4P0.75 | 4x2x0.75 | 12.7 | 214 |
RE-2Y(C)H 6P0.75 | 6x2x0.75 | 14.6 | 278 |
RE-2Y(C)H 8P0.75 | 8x2x0.75 | 15.4 | 324 |
RE-2Y(C)H 12P0.75 | 12x2x0.75 | 17.8 | 427 |
RE-2Y(C)H 16P0.75 | 16x2x0.75 | 19.8 | 526 |
RE-2Y(C)H 20P0.75 | 20.x2x0.75 | 21.5 | 623 |
RE-2Y(C)H 24P0.75 | 24x2x0.75 | 23.1 | 714 |
1.0mm2, Multipair | |||
RE-2Y(C)H 1P1.0 | 1x2x1.0 | 9.4 | 1.3.5 |
RE-2Y(C)H 2P1.0 | 2x2x1.0 | 12.3 | 184 |
RE-2Y(C)H 3P1.0 | 3x2x1.0 | 12.8 | 214 |
RE-2Y(C)H 4P1.0 | 4x2x1.0 | 13.7 | 251 |
RE-2Y(C)H 6P1.0 | 6x2x1.0 | 15.6 | 326 |
RE-2Y(C)H 8P1.0 | 8x2x1.0 | 16.4 | 382 |
RE-2Y(C)H 12P1.0 | 12x2x1.0 | 19.0 | 511 |
RE-2Y(C)H 16P1.0 | 16x2x1.0 | 21.2 | 636 |
RE-2Y(C)H 20P1.0 | 20.x2x1.0 | 23.5 | 775 |
RE-2Y(C)H 24P1.0 | 24x2x1.0 | 25.3 | 892 |
1.3mm2, Multipair | |||
RE-2Y(C)H 1P1.3 | 1x2x1.3 | 9.7 | 140 |
RE-2Y(C)H 2P1.3 | 2x2x1.3 | 12.9 | 204 |
RE-2Y(C)H 3P1.3 | 3x2x1.3 | 13.5 | 242 |
RE-2Y(C)H 4P1.3 | 4x2x1.3 | 14.5 | 285 |
RE-2Y(C)H 6P1.3 | 6x2x1.3 | 16.7 | 375 |
RE-2Y(C)H 8P1.3 | 8x2x1.3 | 17.4 | 444 |
RE-2Y(C)H 12P1.3 | 12x2x1.3 | 20.2 | 599 |
RE-2Y(C)H 16P1.3 | 16x2x1.3 | 22.6 | 750 |
RE-2Y(C)H 20P1.3 | 20.x2x1.3 | 25.1 | 916 |
RE-2Y(C)H 24P1.3 | 24x2x1.3 | 27.0 | 1064 |
Note : Other conductor sizes & core configurations are available upon request
Electrical PROPERTIES
Conductor Area Size | mm 2 | 0.5 | 0.75 | 1.0 | 1.3 | 1.5 | |
Insulation thickness (nominal) | mm | 0.4 | 0.4 | 0.4 | 0.45 | 0.45 | |
Conductor resistance (20°C) | Ω/km | 36.7 | 25 | 18.5 | 14.2 | 12.3 | |
Insulation resistance (20°C) | MΩ.km(Min.) | 5000 | |||||
Mutual Capacitance (1 kHz) | pF/m(Max.) | ||||||
≤ 4 pairs | 115 | 115 | 115 | 120 | 120 | ||
all other pairs | 90 | 90 | 90 | 105 | 105 | ||
Capacitance unbalance(1 kHz) | pF/500 m (Max.) | 500 | |||||
L / R (ratio) (max.) | μH/Ω | 25 | 25 | 25 | 40 | 40 | |
Operating voltage Urms | V | 300 | 300 | 300 | 300 | 300 | |
Test Voltage | Core to Core | V | 1500 | 1500 | 1500 | 1500 | 1500 |
Core to Screen | V | 1500 | 1500 | 1500 | 1500 | 1500 |
RE-2Y(C)H 90°C / 300V
STANDARDS | Basic design to EN 50288-7 |
APPLICATION | Instrument cable minimizes noise and signal interference, delivering clean signals in harsh environments and general manufacturing operations. |
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Sunlight Resistance | UL 1581 section 1200 |
Oil Resistance | ICEA S-73-532** |
Note: Asterisk * denotes superseded standard, **Test temperature +60°C, duration 4h. Retention: min 60% of tensite strength/min.60% of elongation.
VOLTAGE RATING | 300V |
CABLE CONSTRUCTION | |
Conductor: | Annealed copper solid or plain copper stranded to IEC 60228 Class 2. |
Insulation: | PE compound, EN 50290. 2-23. |
Pair: | Two conductors twisted to form a pair |
Lay-up: | Pairs laid up in layers of optimum pitch |
Separator: | Polyester tape |
Overall Screen: | Tinned copper wire braid |
Outer sheath: | Thermoplastic LSZH compound type to EN 50290-2-27. |
COLOUR CODE | |
Insulation: | Black / White, continuously numbered on white core(1, 2..)for multipair. |
Outer Sheath: | Black or blue for intrinsically safe systems |
Physical AND THERMAL PROPERTIES | |
Temperature Range During Operation (Fixed State): | -30°C – +70°C |
Temperature Range During Installation (Mobile State): | -5°C – +50°C |
Minimum Bending Radius: | 7.5 X Overall Diameter |
CONSTRUCTION PARAMETERS
Cable Code | RE-2Y(C)H | ||
No. of Pairsx2xCross Section | Copper Weight | Approx. Weight | |
No.x2xmm2 | Kg/km | Kg/km | |
0.5mm2, Multipair | |||
RE-2Y(C)H 1P0.5 | 1x2x0.50 | 8.3 | 110 |
RE-2Y(C)H 2P0.5 | 2x2x0.50 | 10.7 | 143 |
RE-2Y(C)H 3P0.5 | 3x2x0.50 | 11.1 | 158 |
RE-2Y(C)H 4P0.5 | 4x2x0.50 | 11.9 | 181 |
RE-2Y(C)H 6P0.5 | 6x2x0.50 | 13.6 | 230 |
RE-2Y(C)H 8P0.5 | 8x2x0.50 | 14.2 | 264 |
RE-2Y(C)H 12P0.5 | 12x2x0.50 | 16.4 | 343 |
RE-2Y(C)H 16P0.5 | 16x2x0.50 | 18.2 | 418 |
RE-2Y(C)H 20P0.5 | 20x2x0.50 | 19.7 | 487 |
RE-2Y(C)H 24P0.5 | 24x2x0.50 | 21.1 | 557 |
0.75mm2, Multipair | |||
RE-2Y(C)H 1P0.75 | 1x2x0.75 | 8.7 | 119 |
RE-2Y(C)H 2P0.75 | 2x2x0.75 | 11.4 | 161 |
RE-2Y(C)H 3P0.75 | 3x2x0.75 | 11.9 | 185 |
RE-2Y(C)H 4P0.75 | 4x2x0.75 | 12.7 | 214 |
RE-2Y(C)H 6P0.75 | 6x2x0.75 | 14.6 | 278 |
RE-2Y(C)H 8P0.75 | 8x2x0.75 | 15.4 | 324 |
RE-2Y(C)H 12P0.75 | 12x2x0.75 | 17.8 | 427 |
RE-2Y(C)H 16P0.75 | 16x2x0.75 | 19.8 | 526 |
RE-2Y(C)H 20P0.75 | 20.x2x0.75 | 21.5 | 623 |
RE-2Y(C)H 24P0.75 | 24x2x0.75 | 23.1 | 714 |
1.0mm2, Multipair | |||
RE-2Y(C)H 1P1.0 | 1x2x1.0 | 9.4 | 1.3.5 |
RE-2Y(C)H 2P1.0 | 2x2x1.0 | 12.3 | 184 |
RE-2Y(C)H 3P1.0 | 3x2x1.0 | 12.8 | 214 |
RE-2Y(C)H 4P1.0 | 4x2x1.0 | 13.7 | 251 |
RE-2Y(C)H 6P1.0 | 6x2x1.0 | 15.6 | 326 |
RE-2Y(C)H 8P1.0 | 8x2x1.0 | 16.4 | 382 |
RE-2Y(C)H 12P1.0 | 12x2x1.0 | 19.0 | 511 |
RE-2Y(C)H 16P1.0 | 16x2x1.0 | 21.2 | 636 |
RE-2Y(C)H 20P1.0 | 20.x2x1.0 | 23.5 | 775 |
RE-2Y(C)H 24P1.0 | 24x2x1.0 | 25.3 | 892 |
1.3mm2, Multipair | |||
RE-2Y(C)H 1P1.3 | 1x2x1.3 | 9.7 | 140 |
RE-2Y(C)H 2P1.3 | 2x2x1.3 | 12.9 | 204 |
RE-2Y(C)H 3P1.3 | 3x2x1.3 | 13.5 | 242 |
RE-2Y(C)H 4P1.3 | 4x2x1.3 | 14.5 | 285 |
RE-2Y(C)H 6P1.3 | 6x2x1.3 | 16.7 | 375 |
RE-2Y(C)H 8P1.3 | 8x2x1.3 | 17.4 | 444 |
RE-2Y(C)H 12P1.3 | 12x2x1.3 | 20.2 | 599 |
RE-2Y(C)H 16P1.3 | 16x2x1.3 | 22.6 | 750 |
RE-2Y(C)H 20P1.3 | 20.x2x1.3 | 25.1 | 916 |
RE-2Y(C)H 24P1.3 | 24x2x1.3 | 27.0 | 1064 |
Note : Other conductor sizes & core configurations are available upon request
Electrical PROPERTIES
Conductor Area Size | mm 2 | 0.5 | 0.75 | 1.0 | 1.3 | 1.5 | |
Insulation thickness (nominal) | mm | 0.4 | 0.4 | 0.4 | 0.45 | 0.45 | |
Conductor resistance (20°C) | Ω/km | 36.7 | 25 | 18.5 | 14.2 | 12.3 | |
Insulation resistance (20°C) | MΩ.km(Min.) | 5000 | |||||
Mutual Capacitance (1 kHz) | pF/m(Max.) | ||||||
≤ 4 pairs | 115 | 115 | 115 | 120 | 120 | ||
all other pairs | 90 | 90 | 90 | 105 | 105 | ||
Capacitance unbalance(1 kHz) | pF/500 m (Max.) | 500 | |||||
L / R (ratio) (max.) | μH/Ω | 25 | 25 | 25 | 40 | 40 | |
Operating voltage Urms | V | 300 | 300 | 300 | 300 | 300 | |
Test Voltage | Core to Core | V | 1500 | 1500 | 1500 | 1500 | 1500 |
Core to Screen | V | 1500 | 1500 | 1500 | 1500 | 1500 |